ASTM D2132-23 Dust-and-Fog Tracking and Erosion Resistance of ElectricalInsulating Materials1
VIP免费
1
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards,Guides and Recommendations issued by the World Trade Organizzation Technical Barriers to Trade(TBT)Committee.
TERNATOMAL
Designation:D2132-23
Standard Test Method for
Dust-and-Fog Tracking and Erosion Resistance of Electrical
Insulating Materials¹
This standard is issued under the fixed designation D2132;the number immediately following the designation indicates the year of
original adoption or,in the case of revision,the year of last revision.A number in parentheses indicates the year of last reapproval.A
superscript epsilon(E)indicates an editorial change since the last revision or reapproval
1.Scope*
1.1 This test method is intended to differentiate solid elec-
trical insulating materials with respect to their resistance to the
action of electric arcs produced by conduction through surface
films of a specified contaminant containing moisture.Test
Methods D2302,D2303,D3638 ,and D5288 are also useful to
evaluate materials.
1.2 Units—The values stated in SI units are the standard.
The inch-pound units in parentheses are for information only.
The values stated in each system are not necessarily exact
equivalents;therefore,to ensure conformance with the
standard,each system shall be used independently of the other,
and values from the two systems shall not be combined.
1.3 This standard does not purport to address all of the
safety concerns,if any,associated with its use.It is the
responsibility of the user of this standard to establish appro-
priate safety,health,and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
NoTE 1—There is no equivalent ISO standard.
1.4 This international standard was developed in accor-
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
Development of International Standards,Guides and Recom-
mendations issued by the World Trade Organization Technical
Barriers to Trade(TBT)Committee.
2.Referenced Documents
2.1 ASTM Standards:²
D709Specification for Laminated Thermosetting Materials
D1711Terminology Relating to Electrical Insulation
D2302Method of Test for Differential Wet Tracking Resis-
'This test method is under the jurisdiction of ASTM Committee D09 on
Electrical and Electronic Insulating Materials and is the direct responsibility of
Subcommittee D09.07 on Electrical Insulating Materials.
Current edition approved Aug.1,2023.Published September 2023.Originally
approved in 1962.Last previous edition approved in 2019 as D2132-19.DOI:
10.1520/D2132-23.
²For referenced ASTM standards,visit the ASTM website,www.astm.org,or
contact ASTM Customer Service at service@astm.org.For Annual Book of ASTM
Standards volume information,refer to the standard's Document Summary page on
the ASTM website.
tance of Electrical Insulating Materials with Controlled
Water-to-Metal Discharges (Withdrawn 1982)³
D2303Test Methods for Liquid-Contaminant,Inclined-
Plane Tracking and Erosion of Insulating Materials
D3638Test Method for Comparative Tracking Index of
Electrical Insulating Materials
D5288Test Method for Determining Tracking Index of
Electrical Insulating Materials Using Various Electrode
Materials(Excluding Platinum)
3.Terminology
3.1 Definitions:
3.1.1 For definitions pertinent to this test method see Ter-
minology D1711 .
4.High Voltage Hazard
4.1 Warning—Lethal voltages area potential hazard during
the performance of this test.It is essential that the test
apparatus,and all associated equipment electrically connected
to it,be properly designed and installed for safe operation.
4.2 Solidly ground all electrically conductive parts which it
is possible for a person to contact during the test.
4.3 Provide means for use at the completion of any test to
ground any parts which were at high voltage during the test or
have the potential for acquiring an induced charge during the
test or retaining a charge even after disconnection of the
voltage source.
4.4 Thoroughly instruct all operators as to the correct
procedures for performing tests safely.
4.5 When making high voltage tests,particularly in com-
pressed gas or in oil,it is possible for the energy released at
breakdown to be sufficient to result in fire,explosion,or
rupture of the test chamber.Design test equipment,test
chambers,and test specimens so as to minimize the possibility
of such occurrences and to eliminate the possibility of personal
injury.
NoTE 2—If the potential for fire exists,have fire suppression equipment
available.
3 The last approved version of this historical standard is referenced on
www.astm.org.
*A Summary of Changes section appears at the end of this standard
Copyrighto ASTM International,100 BarrHarborDrive,PO BoxC700,West Conshohocken,PA 19428-2959.United States
5.Summary of Test Method
5.1 With electrodes mounted as shown in Fig.1 ,coat test
specimens with a synthetic dust and test in a chamber shown in
Fig.2. Using the fog nozzle,direct a water spray at the test
specimen.After the surface has been wetted,apply a 60 Hz
voltage between the electrodes.Arcing occurs across localized
high-resistance areas produced by nonuniform evaporation of
the water from the contaminant.These arcs produce high
temperatures in the underlying insulation with resultant car-
bonization of most organic materials.The carbonization con-
centrates the electric field.It is possible further carbonization
will occur in the direction of the field.In such cases,a carbon
track is formed which spans the distance between the elec-
trodes and causes failure.It is possible that materials that do
not track will erode under the action of the arcing.Such erosion
usually progresses from an upper electrode through the thick-
ness of the specimen towards the underlying electrode.
460 mm =18 in.510 mm =20 in.710 mm =28 in.
FIG.2 Dust and Fog Test Chamber,
Minimum Recommended Size
5.2 Rate materials that track in terms of the time required to
form a track between the electrodes.
5.3 Rate materials that do not track in terms of the time
required to erode to failure.
5.4 Failure will be indicated when the current increases
sufficiently to actuate an overcurrent device.
NoTE 3—The conditions o this test favor the formation of a track for
several possible reasons.Most important,the continuous renewal of the
conducting properties of the contaminant by the water spray allows a track
to grow progressively over long periods of time.
of both,if exposed to high relative humidity and contamination
environments.This is particularly true of organic insulations in
outdoor applications where the surface of the insulation be-
comes contaminated by deposits of moisture and dirt,for
example,coal dust or salt spray.This test method is an
accelerated test that simulates extremely severe outdoor con-
tamination.It is believed that the most severe conditions likely
to be encountered in outdoor service in the United States will
be relatively mild compared to the conditions specified in this
test method.
6.Significance and Use
6.1 Method—It is possible that electrical insulation in ser-
vice will fail as a result of tracking,erosion,or a combination
UPPER ELECTRODES
SYNTHETIC
DUST LAYER
GROUND
ELECTRODE
INSULATING
SUPPORT
Metric Equivalents
in.
/B
V2
1
2
mm
3.2
12.7
25.4
50.8
FIG.1 Test Arrangement of Electrode System
6.2 Test Results—Materials can be classified by this test
method as tracking-resistant,tracking-affected,or tracking-
susceptible.The exact test values for these categories as they
apply to specific uses will be specified in the appropriate
material specifications,but guideline figures are suggested in
Note 4. Tracking-resistant materials,unless erosion failure
occurs first,have the potential to last many hundreds of hours
(Note 5).Erosion,though it is possible that it will progress
laterally,generally results in a failure perpendicular to the
specimen surface.Therefore,compare only specimens of the
same nominal thickness for resistance to tracking-induced
erosion.Estimate the extent of erosion from measurements of
the depth of penetration of the erosion.Place materials that are
not tracking-susceptible in three broad categories—erosion-
resistant,erosion-affected,and erosion-susceptible.When the
standard thickness specimen is tested,the following times to
failure typify the categories (Note 6):
Erosion-susceptible
Erosion-affected
Erosion-resistant
NoTE 4—Tracking-susceptible materials usually fail within 5 h.
Tracking-affected materials usually fail before about 100 h.
NoTE 5—This information is derived from the individual experiences of
eight laboratories using this test method since its publication as a
suggested test method in June 1957,and from the results of an organized
test program among these laboratories.
NoTE 6—In a normal distribution approximately 68%of all test values
are included within±1 standard deviation of the mean.
6.3 Interpretation of Test Results—This test method pro-
vides information that allows classification as described in 6.2.
The comparison of materials within the same group is likely to
5h to 50 h
50 h to 200 h
over 200 h
3
D2132-23
be ambiguous unless three or more replicate specimens are
tested.When the test method is used for specification purposes,
do not establish simple minimum values without consideration
of the large variance to be expected in test results.It is
recommended that quality levels and specification minima be
determined by statistical techniques.
7.Apparatus
7.1 General—A schematic diagram of the power supply and
control apparatus for testing one specimen is shown in Fig.
3(a).It is generally desirable to test three or more specimens
simultaneously.It is recommended but not mandatory that a
separate power supply and control be used for each test
specimen.This allows “breaking-in”and recording of time to
failure separately for each specimen.
7.2 Circuit Breaker—The circuit breaker(current relay,OL)
interrupts the power supply on failure and stops the timing
meter.Use it as an ON-OFF switch and as a device for
interrupting air and water supply when all specimens fail. Fig.
3(b)illustrates the air and water supply circuit when three
specimens are tested using one fog nozzle.The circuit breaker
shall be rated at 2 A to 3 A,inverse-time element type,for a
115V supply.Use a resistance,R₀,to shunt the current coil
during the break-in period so that the breaker will not actuate
as a result of the bright-flash currents typical of this period.
Adjust the resistance to produce an effective breaker action at
approximately 6A(115V supply).Remove or switch out the
shunt resistance after break-in.
7.3 Supply Transformer⁴—Use a supply transformer,T₂,
capable of supplying 1500V,60 Hz,rms.A 200 VA potential
transformer is capable of supplying power for up to three
specimens if desired.Use a transformer with a 20:1 ratio when
used with a 115V primary supply.Choose a transformer that
offers an impedance between 600 Ω and 1200 Ω resistance and
200 Ω and 700 Ω reactance.Accomplish this by insertion of
inductance L and resistance R₁in the low-voltage side and
resistance R₂in the high-voltage side.
Westinghouse
purpose.
(a)Power supply and control circuit of wet tracking tests.
(b)Air and water supply circuit.
FIG.3 Circuit Diagrams
7.4 Control Transformer—Use a variable-ratio
autotransformer,T₁,to adjust the voltage as required.
7.5 Voltmeter—Use a voltmeter,V,in the primary side to
determine the specimen test voltage.Alternatively,use a
high-impedance voltmeter for connection in the secondary,in
which case take precautions to prevent electric shock to an
operator.If a voltmeter is used in the primary,calibrate it
against secondary voltage with a secondary load of 10 mA.
7.6 Monitoring Provisions—Use an ac ammeter,A,to moni-
tor specimen current.Use a separate ammeter for each test
specimen.Alternatively make provisions to connect an amme-
ter into each test-specimen circuit.Shunt the ammeter with a
normally closed contact,PB,and a capacitance,C,to protect
the ammeter from the large intermittent currents that occur
during break-in.Connect the capacitance,if used,by a switch,
SA.After the break-in period,open the switch unless the values
of the capacitance and ammeter impedances are such as to
produce negligible error in current measurement.Use terminals
A,B and C,D for oscilloscope monitoring,for current
measurement with a voltmeter in combination with a resistor,
or for insertion of an undercurrent relay to be used to stop the
clock if the scintillation current falls below the specified value.
7.7 Electrodes—Use three copper or brass electrodes 13 mm
by 51 mm by 3.2 mm(0.5 in.by 2 in.by 0.125 in.),with
corners rounded to a 3.2 mm(0.125 in.)radius on the top
surface of the specimen and spaced 25 mm(1 in.)apart as
shown in Fig.1 .Use a ground plate of copper or brass and of
the same size as the test specimen on the bottom surface and
mounted on an insulating support inclined 15 deg to the
horizontal as shown in Fig.1.Clamp the electrodes firmly to
the test specimen.A suggested arrangement is shown in Fig.4.
7.8 Test Chamber—Use acubicle test chamber,Fig.2 ,made
from plastic or metal.The front wall is made of glass or
poly(methyl methacrylate),or contains viewing ports or doors
made of these materials.Make the cubicle at least 510 mm
(20 in.)high and 710 mm(28 in.)wide.Determine the depth by
the number of specimens to be tested.Three specimens require
a minimum depth of 460 mm(18 in.).Fit the chamber with
means for venting near the bottom of the cubicle,preferably
along the end of the chamber where the specimens are located.
Limit the venting area to about 130 cm²(20 in.²)to eliminate
dependence of test results on the ambient humidity.
7.8.1 Mount one or more fog nozzles(Fig.5 )to obtain the
specified uniform moisture deposition on all test specimens.It
is suggested that one fog nozzle,mounted approximately
635 mm(25 in.)straight line distance from the nozzle to the
center specimen at a height of approximately 355 mm(14 in.)
above these specimens,will,with a suitably adjusted deflector,
produce the specified conditions for three test specimens in a
single cubicle (see Fig.2 ).When only one fog nozzle is used
in the cubicle,it is recommended that additional air be
introduced into the cubicle equal to about double that flowing
through a standard fog nozzle connected to an air supply of
0.035 MPa to 0.04 MPa (5 psig to 6 psig).
4General Electric
No.687588,have been
JE41,Model
satisfactory
KAR-3,and
for this
Type VS,Style
Type
found
摘要:
展开>>
收起<<
1ThisinternationalstandardwasdevelopedinaccordancewithinternationallyrecognizedprinciplesonstandardizationestablishedintheDecisiononPrinciplesfortheDevelopmentofInternationalStandards,GuidesandRecommendationsissuedbytheWorldTradeOrganizzationTechnicalBarrierstoTrade(TBT)Committee.TERNATOMALDesignati...
声明:如果您的权利被侵害,请联系我们的进行举报。
相关推荐
-
GB∕T 25915.2-2021 洁净室及相关受控环境 第2部分:洁净室空气粒子浓度的监测
2024-04-17 999+ -
GB∕T 25915.3-2024洁净室及相关受控环境 第3部分:检测方法VIP免费
2024-08-09 97 -
(高清)GB∕T 25915.3-2024 洁净室及相关受控环境第3部分:检测方法VIP免费
2025-08-27 999+ -
GB∕T 16886.1-2025医疗器械生物学评价 第1部分 风险管理过程中生物学安全性评价的要求和通用原则(草案稿)VIP免费
2025-09-02 694 -
GB∕T 191-2025 包装储运图示标志(征求意见稿)VIP免费
2025-09-29 999+ -
GB∕T 19000-2016 质量管理体系 基础和术语(高清)VIP免费
2025-10-27 999+ -
GB∕T 19001-2016 质量管理体系要求
2025-10-27 785 -
GB∕T 16292-2025 医药工业洁净室(区)悬浮粒子的测试方法VIP免费
2025-10-29 999+ -
GB∕T 16292《医药工业洁净室(区)悬浮粒子的测试方法》2010版和2025版对比分析(逐条对比)VIP免费
2025-10-30 434 -
GB∕T 17626.3-2023 电磁兼容 试验和测量技术 第3部分:射频电磁场辐射抗扰度试验
2025-11-24 470
作者:安心365
分类:法规规范
价格:60质量币
属性:6 页
大小:812.86KB
格式:PDF
时间:2026-04-16

